Inspection History Details
Permit: T02CM03370
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 12/09/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PANEL STILL DOES NOTMATCH REVISED PLASN. 2.) USE AN APPROVED LUG CONNECTION FOR GROUNDING LUG AT SES. 3.) PLEASE LABEL BREAKER AT SES. 4.) MAINTAIN WORKING CLEARENCES AT SES. 5.) FEEDER TO BEAS PER PLANS. 6.) FINISH PRECIOUS INSPECTIONS 7.) VERIFY LICENSED ELECTRICAL CONTRACTOR. 8.) SWITCHES BATH NEED AN APPROVED EXTENDER RING METAL NOT APPRV. |
|
| 12/06/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 11/15/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*PANEL SHOW ONLY 4 CIRCUIT BEING USED PANEL PRESENTLY FULL ON 2 30A 2POLE BKRS AND 4-15 AMP CB'S AND 10-20 AMP CB'S TO MUCH FOR 60AMP PNL. REVISE PLAN, IT DOES NOT REFLECT INSTALLATION. OWNER TO TO OBTAIN PERMIT FOR WORK NEXT DOOR LTS. |