Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/20/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) FRAMING TO BE APPROVED WHEN ALL OTHER INTERMEDIATES ARE COMPLETED 2) NEED CAULKING AROUND MAIN GAS PIPE 3) LEAK IN COLD WATER JUNCTION IN MAIN BATHROOM 4) NOT READY |