Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 09/27/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.)MAIN BOND JUMPER IN X-FORMER TO SMALL SHOULD BE 1/0 PER 250 NEC AND PLAN. 2.) SUPPORT FLEX POWER DROPS WITHIN 12" OF TERM, ABOVE CEILING. 3.) NEED LETTER FROM ARCH. FOR USE OF MC CABLE INSTEAD OF CONDUIT PER PLAN NOTE. |
| 09/23/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) X - FORMER 112.5. KVA NOT ALLOWED TO BE INSTALLED ABOVE GRID CEILING PER 450-13 B NEC. 2.) FEEDER WIRE SIZE NOT PER PLAN. 3.) BOND NEUTRAL BAR IN X FORMER TO BLD STEEL, COLD WATER PER 250 NEC. 4.) COMPLETE WIRE PULL, MAKE UP, CONDUIT SUPPORTS ABOVE CEILING WEST WALL. 5.) PLUG UNUSED OPENINGS IN J-BOXES. 6.) CONDUITS TO BE SUPPORTED WITHIN 3' EACH TERMINATION AND EVERY 10' SUPPORT TO STRUCTURE. |
| 09/20/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*COMPLETE WIRE PULL MAKE UP IN J-BOXES, SUPPORT CONDUITS WITHIN 3' OF TERM. GUTTERS. |