Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM03304

Parcel: 12412043A


Addresses:

1230 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02CM03304

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*JERRY ORTA WAS INFORMED OF THIS PROJECTS APPROVAL. HE CLEARED THE PROJECT FOR A NEW DROP BY TEP
08/16/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*A REVISED PLAN FOR THE SERVICE EQUIPMENT AND WIRING MUST BE PREPARED AND SUBMITTED BY THE ENGINEER OF RECORD TO C.O.T. DEVELOPEMENT SERVICE PLAN REVIEWER FOR STAMP AND SIGNATURE. THIS MUST BE COMPLETE BEFORE FINAL WILL BE APPROVED.
08/15/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*A NEUTRAL IN REQUIRE AT A/C DISCONNECT A NEUTRAL IS REQUIRED AT A/C 12 DISCONNECT 2.) BOND ALL DISCONNECT. 3.) LABEL THE 4 DISCONNECT AS SERVICE DISCONNECT. 4.) NEED ACCURATE SERVICE DIAGRAM SHOW ALL WIRES AND SIZES 5.) INSTALL GROUND BACK
08/12/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*OK 2 GROUND RODS & 3/0 CU ELECTRODE COND, ONLY.