Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02CM03304
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2002 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*JERRY ORTA WAS INFORMED OF THIS PROJECTS APPROVAL. HE CLEARED THE PROJECT FOR A NEW DROP BY TEP | |
08/16/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*A REVISED PLAN FOR THE SERVICE EQUIPMENT AND WIRING MUST BE PREPARED AND SUBMITTED BY THE ENGINEER OF RECORD TO C.O.T. DEVELOPEMENT SERVICE PLAN REVIEWER FOR STAMP AND SIGNATURE. THIS MUST BE COMPLETE BEFORE FINAL WILL BE APPROVED. | |
08/15/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*A NEUTRAL IN REQUIRE AT A/C DISCONNECT A NEUTRAL IS REQUIRED AT A/C 12 DISCONNECT 2.) BOND ALL DISCONNECT. 3.) LABEL THE 4 DISCONNECT AS SERVICE DISCONNECT. 4.) NEED ACCURATE SERVICE DIAGRAM SHOW ALL WIRES AND SIZES 5.) INSTALL GROUND BACK | |
08/12/2002 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*OK 2 GROUND RODS & 3/0 CU ELECTRODE COND, ONLY. |