Inspection History: ELECTRIC - FINAL

Permit Number - T02CM03298

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2003 ELECTRIC - FINAL Approved
12/24/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*ALL WORK COMPLETED PLEASE VERIFY LICENSED CONTRATORS A LETTER HEAD LETTER WILL DO.
12/16/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*Please finish items #1 & 4 of previous inspection.
12/09/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*ROOF
1.) TIGHTEN LOOSE SEALTITE FITTINGS.
2.) SUPPORT SEALTITE OVER 3' IN LENGTH.
3.) MISSING GFI COVERS AND INSTALL GFI'S INTO BOXES.
4.) MAINTAIN WORKING CLEARENCE IN FRONT OF DISCONNECTS 36"
11/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*AN APPROVED CONNECTOR IS NEEDED AT HOODS ALSO PLEASE GROUND HOODS.
2.) PLEASE PROVIDE A LADDER FOR INSPECTION OF ROOF NEXT TIME.