Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03298
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2003 | ELECTRIC - FINAL | Approved | ||
12/24/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*ALL WORK COMPLETED PLEASE VERIFY LICENSED CONTRATORS A LETTER HEAD LETTER WILL DO. | |
12/16/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*Please finish items #1 & 4 of previous inspection. | |
12/09/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*ROOF 1.) TIGHTEN LOOSE SEALTITE FITTINGS. 2.) SUPPORT SEALTITE OVER 3' IN LENGTH. 3.) MISSING GFI COVERS AND INSTALL GFI'S INTO BOXES. 4.) MAINTAIN WORKING CLEARENCE IN FRONT OF DISCONNECTS 36" |
|
11/25/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*AN APPROVED CONNECTOR IS NEEDED AT HOODS ALSO PLEASE GROUND HOODS. 2.) PLEASE PROVIDE A LADDER FOR INSPECTION OF ROOF NEXT TIME. |