Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2003 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection 0000*SENT TO TEP ON 3/25/03 AT 9:15AM OK TO CLEAR FOR TEMP POWER FOR TEST SUBJECT TO BOND POSTING & SIGN OFF SHEET COMPLETE OR APPROVAL OTHER INSPECTORS. | |
| 03/24/2003 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection 0000* 1.) EXTENDER RINGS WILL BE NEEDED WHERE MORE THAN 1/4" FROM BOX TO FLUSH. 2.) MISSING DEVICES & PLATES. 3.) PLEASE PROVIDE FUSES AND REJECTION PINS 4.) BRACING OF CONDUCTOR AS PER MANUFACTURE IS NEEDED. 5.) BONDING JUMPER TO BE SIZED PER 250-102 & 250 -66. FOR 2ND SERVICE. |