Inspection Status: Partial Approval
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SAFETY GLASS, TOILET COMPARTMENT CAN BE VERIFIED AT FINAL INSPECTION 2) I DON'T RECALL IF WE TALKED ABOUT HEATING FOR ROOMS AT LAST INSPECTION PLEASE CALL ME. NOT ON PLAN |
| 10/15/2002 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) ISOLATE COPPER AT BANG PLATE TOP PLATE LAUNDRY MISSING NAIL TO 1/2" PIPE STRAP 2) NEED ROMEX CONNECTOR AT EXISTING LIGHT 3) T&P LINE TO HAVE 1/8" PITCH 4) ONLY 2 FIXTURES FROM A 1/2" LINE YOU HAVE HOSE BIB LAUNRY SINK AND WASHER 5) INSTALL OUTLETS PER PLAN ENTRY, NOT BEHIND DOOR 6) INSTALL DUCT FOR LAUNDRY FAN 7) LAUNDRY TRAY DRAWING ON BACK PAGE 8) REVENT FOR SHOWER TO BE AT 42" 9) 30" FOR WATER CLOSET COMPARTMENT 15" TO CENTER 10) EXHAUST DUCT BATH 11) BATH OUTLET TO BE ON IT'S OWN 20 AMP CIRCUIT 12) WATER LINES UNDER SIZED, START WITH 3/4" OFF WATER HEATER FEED TWO FIXTURES THEN GO BACK TO 3/4" FEED TWO MORE 13) MAKE UP ALL ELECTRIC IN BOXES BOND AND ALL METAL BOXES WITH A GROUND WIRE AND SCREW 14) WINDOW AT REAR NEXT TO DOOR TO BE SAFETY GLASS, SLIDING PANEL 15) PROTECT WET BAR DRAIN FROM DRYWALL NAILS 16) FAN BOXES TO BE STAMPED APPROVED FOR FAN USE |