Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 11/5/02 AT 9:15AM OK CABLE DROP & TEMP POWER FOR CONSTRUCTION #2 & REENERGIZE #1 OK ROUGH ELECT. |
| 11/01/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*1.) PROTECT TEMP CABLE FROM SHARP METAL EDGES, ALSO SUPPORT UP OFF OF GROUND 2.) INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMANAL LUG 3.) FILL UNUSED OPENINGS IN PANEL 4.) SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING 5.) PLEASE HAVE ELECTRICAN PRESENT TO OPEN UP SERVICE EQUIPMENT 6.) TIGHTEN LOOSE FITTING 7.) USE AN APPROVED DEVICE FOR GROUND TERMANATION IN BOXES 8.) SUPPORT SE CABLES IN WALLS 9.) SUPPORT M/C CABLE WITHIN 12" OF FITTING BOX. 10.) USE AN APPROVED CONNECTOR FOR CABLE TO BOX BRING OUT TO FLUSH WITH FINISHED SURFACE 11.) REMOVE CONDUCTOR IN CONDUIT FOR BOXES TO BE COVERED. 12.) WE HAVE OVER FILLED BOXES. |