Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T02CM03289
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2002 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
09/16/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) ROOF GAS PACK REQUIRES LISTED GAS SHUT OFF VALVE AND GAS CONNECTOR INSTALLED 2) ABS PLASTIC VENT ON ROOF REQUIRES PROTECTING WITH LATEX PAINT 3) A MAINTENANCE GFCI OUTLET REQUIRED WITHIN 25' OF ROOF MECHANICAL UNIT 4) UNDERGROUND ELECTRIC CONDUIT MUST BE 18" BELOW GRADE OR 2" CONCRETE CAP 5) FLEX VENT CONNECTOR NOT ALLOWED ON WATER HEATER 6) DISHWASHER REQUIRES VENT LOOP WITHIN 2" OF FLOOD RIM 7) BEDROOMS REQUIRE BATTERY OPERATED SMOKE DETECTORS |