Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 12/05/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) EXISTING UNIT ON NEW ADDITION PANEL ON NORTH WALL YOU HAVE A 100A AB FEEDING #6 AL INTO HOUSE TOO LARGE CONNECT BREAKER SIZE THIS IS NOT ON PLAN WILL IT STAY? 2.) WIRING IN CEILING BED ROOM #12 CU AND #6 AL PULLED OUT OF ROOF PENTRATIONS. 3.) RECEPTACLE MISSING CIR 23 ON WALL NORTH OF WASHER & DRYER RM CIRCLED ON PLAN 4.) RECEPTACLE FOR FIRE PLACE HEATALATOR? OMITED? UNIT B. 5.) 2ND FLOOR "B" GROUND CEILING FAN BOX TO SCREW, BOTH BEDROOM 6.) 2ND FLOOR "B" NE BED ROOM SD TO BE 3' AWAY FROM AC DUCT. 7.) 2ND FLOOR SEAL HOLE ON FIXTURE IN WASHER & DRYER RM CEILING. |