Permit: T02CM03265

Parcel: 123151200


Addresses:

832 E ADAMS ST #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM03265

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/02/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/20/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) WE HAVE DAMAGED ALUM. CONDUCTORS CAN NOT "RING" PER MANUFACTURES REQUIREMENTS.
2.) RECEPTACLE NEEDED AT END OF PENISULA 210-52.
3.) COUNTER RP RECEPTICALES TO BE GFI PROTECTED.
4.) BATH RECEPTICALES TO BE INSTALLED AS PER 210-8.
5.) WIRE GFI OUTSIDE CORRECTLY.
CK ROOF NEXT TIME.