Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03265
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
12/20/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) WE HAVE DAMAGED ALUM. CONDUCTORS CAN NOT "RING" PER MANUFACTURES REQUIREMENTS. 2.) RECEPTACLE NEEDED AT END OF PENISULA 210-52. 3.) COUNTER RP RECEPTICALES TO BE GFI PROTECTED. 4.) BATH RECEPTICALES TO BE INSTALLED AS PER 210-8. 5.) WIRE GFI OUTSIDE CORRECTLY. CK ROOF NEXT TIME. |