Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03251
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CONTRACTOR MAKING REPAIRS | |
| 08/22/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED | |
| 08/19/2002 | ELECTRIC - FINAL | Not ready for Inspection | 1) ALL UNITS ARE LOCKED NO PAPERWORK, NO ONE ON SITE | |
| 08/16/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) UNIT LOCKED, NO REPAIRS MADE TO MAIN PANEL | |
| 08/15/2002 | ELECTRIC - FINAL | Denied | 1. PROVIDE PROPER INTERIOR COVER FOR MAIN PANEL. 2. BRKRS ARE NOT PROPERLY LABELED.PANEL HAS 100AMP MAIN AT 220 V.A.C. YOU HAVE 8ADDITIONAL BREAKER. 5 ARE LISTED ON YOUR LAVEL. 3. CANNOT HAVE EMPTY SPACES FOR BREAKERS. 4. PLEASE VERIFY THIS UNIT IS AN ORIGINAL 2 WIRE SYSTEM. 5. TEST UNIT SHOWS OPEN GROUND AT ALL RECEPTCALES AND GFCI 6. UNIT 3. POWER TO GFCI ON N. WALL OF KITCHEN, REFRIGERATOR AND ALL OTHER OUTLETS ARE NON OPERATIONAL. ALL BREAKERS IN MAIN PANEL FOR THIS UNIT ARE ON |
|
| 08/14/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 07/15/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |