Permit: T02CM03251

Parcel: 122181810

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM03251

Inspection Description - ELECTRIC - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
09/06/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) CONTRACTOR MAKING REPAIRS
08/22/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED
08/19/2002 ELECTRIC - FINAL Not ready for Inspection 1) ALL UNITS ARE LOCKED NO PAPERWORK, NO ONE ON SITE
08/16/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) UNIT LOCKED, NO REPAIRS MADE TO MAIN PANEL
08/15/2002 ELECTRIC - FINAL Denied 1. PROVIDE PROPER INTERIOR COVER FOR MAIN PANEL.
2. BRKRS ARE NOT PROPERLY LABELED.PANEL HAS 100AMP MAIN AT 220 V.A.C. YOU HAVE 8ADDITIONAL BREAKER. 5 ARE LISTED ON YOUR LAVEL.
3. CANNOT HAVE EMPTY SPACES FOR BREAKERS.
4. PLEASE VERIFY THIS UNIT IS AN ORIGINAL 2 WIRE SYSTEM.
5. TEST UNIT SHOWS OPEN GROUND AT ALL RECEPTCALES AND GFCI
6. UNIT 3. POWER TO GFCI ON N. WALL OF KITCHEN, REFRIGERATOR AND ALL OTHER OUTLETS ARE NON OPERATIONAL. ALL BREAKERS IN MAIN PANEL FOR THIS UNIT ARE ON
08/14/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
07/15/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*