Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM03249
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/03/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) MISSED P.A. REAR WALL 2) BLOCK FIREPLACE DIRECT VENT 3) STRAP WALL AT GARAGE C SHEAR PER 7/A8 4) SECURE CONDENSATE 5) BANG PLATE WATER EAST WALL KITCHEN 6) ATTACH SHED ROOF TO WALL DIAPHRAM NOT NAILED 7) REMOVE BLOCK AT OVAL B VENT 2ND FLOOR BATH 8) 2ND FLOOR BLOCKS FOR SHEAR |