Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/03/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/21/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) ELECTRIC SUB PANEL NEXT TO MAIN PANEL NOT ON PLAN AND NOT APPROVED FOR EXTERIOR USE 2) ELECTRIC PANEL NEXT TO GAS LINE-NOT ON PLAN (CORRECT PLAN AND OBTAIN CITY OF TUCSON APPROVAL OR BUILD PER PLAN) 3) LOOSE END OF 4-GANG ELECTRIC BOXES MUST BE SECURED 4) FRAMING WITHELD FOR ELCTRIC |
| 01/06/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) MAKE UP GROUND IN ALL BOXES 2) INSERT HOME RUNS INTO PANEL 3) STUCCO MESH MUST BE COMPLETE FOR APPROVAL OF INTERMEDIATE INSPECTION |