Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T02CM03243

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/27/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
11/14/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) ITEMS 1, 2, 3, 6 AND 10 FROM 11/7/02 NOT COMPLIED WITH
11/07/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) SHEAR WALLS MUST BE NAILED TO STUDS SPACED NOT MORE THAN 16" ON CENTER 2) SHEAR WALLS MUST BE NAILED TO STUDS WITH HOLDOWNS INSTALLED 3) PORCH POSTS NOT PER 7/5 AT TOP 4) PROVIDE PROOF OF LEDGER CLIPS PER 1,2-89/5 5) 7/5 NOT COMPLIED WITH 6) HOLDOWN NOT INSTALLED MISSSED PROVIDE APPROVED RE-ENGINEERING REPAIR 7) PLAN CALLS FOR BCI 500 ROOF JOIST. TJI 250 JOIST USED 8) SOME TRUSSES NOT PROPERLY CLIPPED 9) INTERIOR SHEAR WALLS NOT CLIPPED 10) HOLDOWNS CANNOT DEFORMED (BENT) 11) STOPPED INSPECTION, YOU MUST FOLLOW THE PLAN