Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM03243
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/27/2002 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
11/14/2002 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) ITEMS 1, 2, 3, 6 AND 10 FROM 11/7/02 NOT COMPLIED WITH | |
11/07/2002 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) SHEAR WALLS MUST BE NAILED TO STUDS SPACED NOT MORE THAN 16" ON CENTER 2) SHEAR WALLS MUST BE NAILED TO STUDS WITH HOLDOWNS INSTALLED 3) PORCH POSTS NOT PER 7/5 AT TOP 4) PROVIDE PROOF OF LEDGER CLIPS PER 1,2-89/5 5) 7/5 NOT COMPLIED WITH 6) HOLDOWN NOT INSTALLED MISSSED PROVIDE APPROVED RE-ENGINEERING REPAIR 7) PLAN CALLS FOR BCI 500 ROOF JOIST. TJI 250 JOIST USED 8) SOME TRUSSES NOT PROPERLY CLIPPED 9) INTERIOR SHEAR WALLS NOT CLIPPED 10) HOLDOWNS CANNOT DEFORMED (BENT) 11) STOPPED INSPECTION, YOU MUST FOLLOW THE PLAN |