Permit: T02CM03239

Parcel: 123153200


Addresses:

1141 E ELM ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/06/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
01/03/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*SCREWS STILL MISSING AT FRONT UNITS COVER AT SUB PANEL AS DISCUSSED?
01/02/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PROPERLY APPLY ANTI OX PASTE AROUND ALL OF THE CONDUCTOR AT TERMINATION
2.) ISOLATE NEUTRAL & GROUNDING CONDUCTORS AT THE SUB PANEL ( INSTALL SCREWS FO RTHE FRONT COVER TOO.
12/20/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) PLEASE PROVIDE MANFACTURES PAPERWORK FOR LUG KIT IN PANEL #1.
2.) USE AN APPROVED FILLER BLANK.
3.) WE HAVE DAMAGED ALUM, CONDUCTORS, ALSO MANUFACTURES STATES CAN NOT "RING" CONDUCTORS.
4.) USE APPROVED FITTING AT LB AND TIGHTEN LOOSE FITTINGS.
5.) CORRECTLY REMOVE OLD LABELING TAPE OVER NOT APPROVED
6.) COUNTER TOP RECEPTICALE TO BE GFI PROTECTED
7.) PROTECT CABLE BEHIND BATH LIGHTS
8.) BATH OUT LETS TO BE WIRED AS PER 210-8.
9.) FILL UNUSED OPENING IN PANEL #1 AND PLEASE LABEL COVER.
10.) FINISH ROOF.