Permit: T02CM03218

Parcel: 13320002A


Addresses:

850 N BARBARA WORTH

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/23/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/19/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) CANNOT DOUBLE LUG WITH UNLIKE CONDUCTORS SIZE AND MATERIAL CU/AC
08/15/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) NEED OVER CURRENT PROTECTION AND DISCONNECTING MEANS AT SERVICE. ATTACHEMENT FOR CIRCUIT SERVICING SOLAR UNIT