Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM03217

Parcel: 132150220


Addresses:

810 E 47TH ST #106

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/03/2009 ELECTRIC - INTERMEDIATE Approved
09/25/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) NEC 400-8 CARD NOT PERMITTED AS THE PERMANENT WIRING METHOD. HEAVY EQUIPMENT, NON PORTABLE FASTENED IN PLACE TO BE WIRED BY OTHER ACCEPTABLE METHODS OTHER THAN CORD. AGATHON CORD IN POOR CONDITION. 2.) NEED CONTRACTOR TO MAKE CORRECTION PER LETTER. 3.) THE SPACE SAVER 2000 MACHINE IS SUBFED WITH NON METALIC FLEX GREATER THAN 6FT. AND IN AN AREA WHERE IT IS SUBJECT TO PHYSICAL DAMAGE. 4.) NEED AN APPROVED SET OF ELECTRICAL PLANS FOR THIS SPACE TO SHOW ALL EQUIPMENT SHOW PANEL SCHEDULE.
07/09/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*INTERMEDIATE IN FOR TEMP POWER FOR TEST AND CLEAN UP OF BURNED AREA. WILL NEED COMPANY LETTER FROM LICENSED ELECTRICAL CONTRACTOR STATING IN PART THAT ALL WIRING HAS BEEN METERED MEGGERED TESTED OR AND THAT ALL REMAIN CIRCUITS ARE SAFE FOR RE ENERGIZING AND ALL ISOLATED THE GENERAL CONTRACTOR MUST OBTAIN A CERTIFICATE OF OCCUPANCY FOR A FINAL APPROVAL BY ALL TRADES A PLAN OF THE AFFECTED AREA SPACE 106. WILL BE REQUIRED ALL EQUIPMENT TO BE LABELED BY A QUALIFIED TEST LAB. SUCH AS U.L.