Permit: T02CM03205

Parcel: 110065410


Addresses:

2987 N CARDELL CI

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/06/2002 FRAMING Approved IVRS - Inspection 0000*
11/05/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY PER MIKE
11/04/2002 FRAMING Denied IVRS - Inspection 0950*/ 1) POST BASES ARE MISSING THROUGHOUT HAVE ENGINEER OF RECONNECT PROVIDE DOCUMENTATION IF ONLY TWO POST BASES ARE REQUIRED ON ALL POSTS INDICATED ON S2.1 AND FRAMING PLAN REQUIRE POST BASES AND PROVIDE APPROVED REPAIR IF ALL REQUIRED 2) HOLDOWNS MISSING AT INTERIOR SHEARWALLS 3) ANCHOR BOLTS MISSING THROUGHOUT 4) HOUSES MUST BE LATHED FOR INTERMEDIATE INSPECTION, YOU WERE NOTIFIED 10/28/02 5) STOPPED INSPECTION, SUPERINTENDENT MUST INSURE HOUSE IS COMPLETE AND READY FOR INSPECTION PRIOR TO CALLING FOR INSPECTION, YOU MAY BE CHARGED RE-INSPECTION FEE FOR ANY FUTURE FAILURES
11/01/2002 FRAMING Denied IVRS - Inspection 0950*/ 1) CANNOT INSPECT INTERMEDIATE ITEMS, UNTIL LATH HAS BEEN INSTALLED AND APPROVED
10/28/2002 FRAMING Denied IVRS - Inspection 0950*/ NOTE: WE NO LONGER INSPECT INTERMEDIATES PRIOR TO LATH APPROVAL 1) POST BASES MISSING SEE PAGE S2-NOTE 15 2) HOLDOWNS NOT INSTALLED AT INERIOR 3) STAIRS DO NOT COMPLY WITH IRC SECTION 314 FOR RISE OR RUN 4) STOPPED INSPECTION