Permit: T02CM03192

Parcel: 122173650

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/25/2003 FRAMING Approved IVRS - Inspection 0000*
02/21/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) ELECTRICAL SPLICE MUST BE MADE IN AN APPROVED BOX AND MUST BE ACCESSIBLE 2) OPEN LOWER COMBUSTION/RELIEF OPENING TO WATER HEATER CLOSET 3) AN AIR PRESSURE TEST WILL BE REQUIRED ON ALL GAS LINE EXTENSIONS