Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM03187
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE OK FOR C OF O. | |
11/01/2002 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000*CANVAS CONNECTORS STILL NOT COVERED FROM SEWER. 2.) FINISH INSTALLING EXHAUST EQUIPMENT 3.) PLANS CALL FOR VIOLATION ISOLATORS UNDER ALL ROOF MOUNTED EQUIPMENT. | |
10/03/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0935*NO CORRECTIONS HAVE BEEN MADE AT THIS TIME PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. CHECK ALL A/C UNITS FOR PROPER FUSING. | |
09/27/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) SEWER VENT STILL NOT EXTENDED 2) UNITS NOTPERMANENTLY LABELED 3) ELECTRIC DISONNECT OVER FUSED ON SAME UNITS 4) PROVIDE COVERS OVER CANVAS CONNECTORS RECALL FOR FINAL | |
09/23/2002 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) RAISE SEWER VENT 2' ABOVE OUTSIDE AIR INTAKE 2.) PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE ROOF. 3.) UNIT OVERFUSED A/C EQUIPMENT NOT READY FOR INSPECTION AT THIS TIME. |