Permit: T02CM03187

Parcel: 12101103E


Addresses:

6296 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/12/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE OK FOR C OF O.
11/01/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*CANVAS CONNECTORS STILL NOT COVERED FROM SEWER. 2.) FINISH INSTALLING EXHAUST EQUIPMENT 3.) PLANS CALL FOR VIOLATION ISOLATORS UNDER ALL ROOF MOUNTED EQUIPMENT.
10/03/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0935*NO CORRECTIONS HAVE BEEN MADE AT THIS TIME PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. CHECK ALL A/C UNITS FOR PROPER FUSING.
09/27/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) SEWER VENT STILL NOT EXTENDED 2) UNITS NOTPERMANENTLY LABELED 3) ELECTRIC DISONNECT OVER FUSED ON SAME UNITS 4) PROVIDE COVERS OVER CANVAS CONNECTORS RECALL FOR FINAL
09/23/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) RAISE SEWER VENT 2' ABOVE OUTSIDE AIR INTAKE 2.) PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE ROOF. 3.) UNIT OVERFUSED A/C EQUIPMENT NOT READY FOR INSPECTION AT THIS TIME.