Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM03187
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
09/19/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0245*1.) GROUNDING ELECTRODE CONDUCTOR FOR BOTH SERVICES TO BE INTERCONNECTED PER ART 250. 2.) GROUNDING ELECTRODE SPLICE TO BE IRREVERSIBLE. 3.) FLEXABLE CORD DROPS THRU SUSPENDED CEILING NOT APPROVED WIRING METHOD 400-8. | |
09/18/2002 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000* |