Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM03147
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/17/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) STOPPED RE-INSPECTION 2) PLANS/PERMIT NOT ON SITE | |
12/13/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) TRUSS REPAIR 2) DIVERTER STUD 3) ROMEX A.C. UNITS | |
12/11/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) DOUBLE 2 X 10 USED AT 3RD BAY IN LIEU OF 4 X 10 2) MOVE PEX PIPE 12" FROM FLUE WATER HEATER 3) 6/SD2 SPOT NAIL 3" ON CENTER 4) 1ST FLOOR DIVERTER STUD NOTCHED TO DEEP 5) A/C UNITS ROMEX WEST WALL BANG PLATE TOP PLATE 6) HAVE TRUSS CO CHECK 3 TRUSS IN FOM SOUTH WALL 2ND FLOOR ROOF DAMAGE PLATE AND CRACKS BOTH SIDES OF INT. BEARING 7) SD-2 DETAIL IA-SHEAR TRUSS ENDS P-1 PLEASE EXPLAIN, ALSO SEE PLYWOOD PANELS AT BEARING 8) 1/SD2 FLAT FLOOR TRUSS (BAND OSB NOT INSTALLED) |