Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 11/07/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) OLD SERV IS NOW A SUB-PANEL, CLEAN UP WIRING, 2 CIRCUITS ON A SINGLE BREAKER 2) A J-BOX CU. TO ? WIRE SPLICE UNCOVER SPLIT BOLTS, BOLTS TO BE LISTED AND LABELED FOR DISIMILLAR METAL, INSTALL ON LID SOME TYPE OF INSULATER WRAPPED BOLTS ARE PRESSED UP AGAINST COVER WHEN CLOSED 3) METHOD OF FEEDING NEW PANEL, I NEED TO RESEARCH, IF TAP RULE APPLIES ? 4) NEED A GAS BOND AND WATER BOND 5) WILL HAVE ANSWER TOMORROW A.M. |
| 10/17/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SMALL PANEL AT NORTH SIDE OF WALL, WHERE IS POWER COMING FROM ? CAN'T DOUBLE LUG OUT OF 200 AMP MAIN ? |
| 10/15/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) ARRIVED AT 10:00 AM, NO ANSWER |