Permit: T02CM03135

Parcel: 127101310


Addresses:

6249 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/20/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/07/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) OLD SERV IS NOW A SUB-PANEL, CLEAN UP WIRING, 2 CIRCUITS ON A SINGLE BREAKER 2) A J-BOX CU. TO ? WIRE SPLICE UNCOVER SPLIT BOLTS, BOLTS TO BE LISTED AND LABELED FOR DISIMILLAR METAL, INSTALL ON LID SOME TYPE OF INSULATER WRAPPED BOLTS ARE PRESSED UP AGAINST COVER WHEN CLOSED 3) METHOD OF FEEDING NEW PANEL, I NEED TO RESEARCH, IF TAP RULE APPLIES ? 4) NEED A GAS BOND AND WATER BOND 5) WILL HAVE ANSWER TOMORROW A.M.
10/17/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) SMALL PANEL AT NORTH SIDE OF WALL, WHERE IS POWER COMING FROM ? CAN'T DOUBLE LUG OUT OF 200 AMP MAIN ?
10/15/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) ARRIVED AT 10:00 AM, NO ANSWER