Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/14/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 5/15/03 AT 9:15AM |
| 05/12/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*THE CONDUCTORS FROM METER TO 200 A CIRCUIT BREAKER MUST BE #3/0 COPPER MINIMUM SEE TABLE 310-16. CHANGE & RECALL INSPECTION. |
| 05/09/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*LOCK NUTS MISSING ON PIPES. |