Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03126
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 5/15/03 AT 9:15AM | |
05/12/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0210*THE CONDUCTORS FROM METER TO 200 A CIRCUIT BREAKER MUST BE #3/0 COPPER MINIMUM SEE TABLE 310-16. CHANGE & RECALL INSPECTION. | |
05/09/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*LOCK NUTS MISSING ON PIPES. |