Permit: T02CM03126

Parcel: 10610001A


Addresses:

3905 N ROMERO RD 01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/14/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 5/15/03 AT 9:15AM
05/12/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210*THE CONDUCTORS FROM METER TO 200 A CIRCUIT BREAKER MUST BE #3/0 COPPER MINIMUM SEE TABLE 310-16. CHANGE & RECALL INSPECTION.
05/09/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*LOCK NUTS MISSING ON PIPES.