Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03083
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
12/19/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) SUPPORT M/C CABLE AS PER CODE 12" FROM BOX OR FITTING & TIGHTEN LOOSE FITTINGS. 2.) PROTECT M/C CABLE FROM BEING DAMAGE ON CAT WALKS. 3.) BONDING CONDUCTOR TO BE SAME SIZE ENTIRE LENGTH. WIRE HAS BEEN TRIMED AT LUG. 4.) WE HAVE MULTIPOLE TERMANATIONS AT GROUND LUG. 5.) USE AN APPROVED METHOD FOR STRAPPING AT FRONT SOFFET THHN IS NOT APPROVED. 6.) TIGHTEN FIXTURE MOUNTING SCREWS. 7.) APPROVED EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE METAL NOT APPROVED. |