Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM03083
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
12/19/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* 1.) SUPPORT M/C CABLE AS PER CODE 12" FROM BOX OR FITTING & TIGHTEN LOOSE FITTINGS 2.) PROTECT M/C CABLE FROM BEING DAMAGED ON CAT WALKS. 3.) BONDING CODUCTOR TO BE SAME SIZE ENTIRE ENTIRE LENGTH. WIRE HAS BEEN TRIMED AT LUG. 4.) WE HAVE MULTIPOLE TERMANANTIONS AT GROUND LUG. 5.) USE AN APPROVED METHOD |