Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM03056
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FOR POWER ON RECON OK C OF O. PLEASE HAVE PLUMB FINAL AND C OF O . | |
| 07/30/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) MIXER ROLLER OVEN DO NOT HAVE A LISTING SUCH AS UL OR OTHER. 2.) SE CABLE IN CEILING TO BE SUPPORTED AND LIFTED OF FIXTURES AN CEILING. 3.) CONTRACTOR CANNOT BE INSTALLED IN PANEL VOIDS PANELS LISTING. 4.) REMOVE DOUBLE LUGGING IN PANEL. | |
| 07/17/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |