Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM03056
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2002 | ELECTRIC - INTERMEDIATE | Approved | ||
| 07/17/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*PLEASE REVISE PANEL SCHEDULE TO REFLECT ACCURATELY AS BUILT SHOW NAME OF ALL EQUIPMENT. THE OVEN DOES NOT APPEAR TO BE INCLUDED ON PLAN. AREA SHOWS A 6KVA220V. RECEPT. INFACT THE OVEN IS RATED 2.75 KVA. THE CALCAULATED LOAD ALREADY BEING 97.5 AMPS. |