Permit: T02CM03051

Parcel: 130152340


Addresses:

4558 E 25TH ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/20/2002 FRAMING Approved IVRS - Inspection 0000*
08/15/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) ROMEX CONNECTORS 2) MOVE WIRE AT CEILING TO WALL CANNOT BE BURIED BELOW DRYWALL 3) ADD STUD AT WINDOW 4) #8D GALVINIZED TO NAIL EXTERIOR SIDING 4) OK TO INSULATE
08/14/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) FINISH FRAMING FOR WINDOW 2) FINISH INTERIOR ELECTRIC 3) OPEN WIRE SPLICES TO BE INSIDE A BOX, BOX COVER TO BE FLUSH WITH FINISHED DRYWALL 4) NEED OUTLET ON SOUTHWALL UNDER WINDOW CONNECT CONDUIT TO BOX
08/06/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NO ANSWER AT FRONT DOOR, 2ND STOP
07/31/2002 FRAMING Not ready for Inspection 1) NOT READY, NO ANSWER AT DOOR
07/29/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) OUTLETS REQUIRE 6" FROM ANY OPENING 2) HVAC UNIT REQUIRES A 20 AMP #12 COPPER WIRE. THIS CIRCUIT FOR A/C UNIT ONLY NO OTHER APPLIANCES OR LOAD 3) DON'T USE EXTENSION CHORD IN WALL 4) ALL BOXES REQUIRE ROMEX CONNECTORS AND GIRDER SCREW OR USE PLASTIC BOX 5) SMOKE DETECTORS REQUIRED IN ALL BEDROOMS 6) USE UF WIRE AT EXTERIOR CONDUIT FROM SERVICE TO ROOF OVER HANG