Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM03050

Parcel: 120071560


Addresses:

225 W LINCOLN ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM03050

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
08/23/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) FOR #10 WIRE 30 AMP FUSE SIZE IS MAX. 2.) TRAP CONDENSATE DRAIN. 3.) PAINT PVC PIPING, BLOCK CLAMP.
08/15/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*