Permit: T02CM03050

Parcel: 120071560


Addresses:

225 W LINCOLN ST


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM03050

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
08/16/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) NO CONTRACTOR ON JOB SITE. NEW SUPPLY/RETURN DUCTS ABOVE. 2.) NEW CEILING IN ATTIC. 3.) IS THERE AND APPROVED PLAN?
08/15/2002 MECHANICAL - INTERMEDIATE Denied 1.) PROVIDE 240V 30 AMP CIRCUIT FROM SERVICE PANEL TO A/C DISCONNECT. USE #10 WIRE.