Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/11/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/10/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/1) EXPOSED CONTROL WIRING AT CONDENSING UNITS, PROTECT AS PER ART. 300-4. 725, SEC. 725.C. 2) CHECK FUSING AT ALL CONDENSORS- MUST FALL IN BETWEEN MIN. AND MAX. AS LISTED ON DATA PLATE. 3) COMPLETE CLAMPING REFRIG. LINES ON UNISTRUT BRACKET. |