Permit: T02CM03047

Parcel: 116122830

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/11/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
09/10/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/1) EXPOSED CONTROL WIRING AT CONDENSING UNITS, PROTECT AS PER ART. 300-4. 725, SEC. 725.C. 2) CHECK FUSING AT ALL CONDENSORS- MUST FALL IN BETWEEN MIN. AND MAX. AS LISTED ON DATA PLATE. 3) COMPLETE CLAMPING REFRIG. LINES ON UNISTRUT BRACKET.