Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM03037
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 3/11/03 AT 9:15AM OK TO CLEAR. | |
03/04/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0210*THE SERVICE EQUIPMENT GROUNDING "UFER" IS MISSING. THE OFFSET NIPPLES IN GUTTER MUST BE BONDED TO THE METAL OF THE GUTTER. 2.) THE SERVICE CONDUCTORS MUST BE SPLICED TO THE PANEL FEEDERS. 3.) WHAT PROVISIONS TO SUB FEED UNIT A ARE TO BE MADE? 4.) INSTALL A 1/2" K-0 SEAL IN FAN BOX IN NORTH B-RM. 5.) RECESSED LITE CANS NOT IN. |