Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/13/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) THE DISTANCE OF A 2" TRAP ARM FROM TRAP TO VENT IS 5' 1994 UPC TABLE 10-1 2) DETAIL 17 H2A10 H.25'S MISSING 3) PROVIDE DETAIL SHOWING GLU LAM CONNECTION AND BEARING POINT ON GARAGE BEAM 4) ELECTRIC NOT COMPLETE OUTSIDE GARAGE 5) REPAIR SHEARWALL AT GARAGE EAST WALL 6) STRAPS AT DOUBLE TOP PLATE IN GARAGE PROTECTING PLUMBING MUST BE 16G WITH 6, 16D NAILS ON EACH SIDE |
| 02/04/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) 1 SHEARWALLS CALL FOR 3-1/2" A.B.'S AT EACH PANEL 2) GARAGE GLU LAM CALLS FOR 3-2X6 POSTS 3) 9-A10 PROVIDE WEB STIFFENERS FOR TJI'S 4) 15-A10-1212L STRAP #TIES NOT VISIBLE 5) A9-2ND STORY SHEARWALLS CALL FOR SHEATHING ON BOTH SIDES 6) SOUTH GABLE TRUSS NEEDS TIE DOWN TO GIRDER 7) NEED ALTERNATE HOLDOWNS WHERE SLAB EDGE IS SPAULLED 8) PROVIDE TRUSS CALCS 9) EXPOSE COLUMN AT SOUTHEAST CORNER FOR VISUAL EVALUATION TAKE PCOTT AT TCP 10) MOST DUCT BOOT SIZES AND LOCATIONS DIFFER FROM PLAN 12) CORRECT VENT LOCATION IN GARAGE CEILING 13) BANG PLATE WIRES AT: LIVING ROOM NORTH WALL, DOWN HALLWAY WEST TOP PLATES, DOWN STORAGE WEST WALL, TOP PLATE GARAGE WEST WALL, TOP PLATE EAST OF HER CLOSET 14) FINISH WIRING WEST GARAGE WALL 15) GROUND ALL METAL BOXES 16) NOTE: CLAMP FIREPLACE DAMPER OPEN FOR FINAL |