Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/15/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000*1.) PER PRESUMED 60PST @ RAFTER 24"OC 9' SPAN =28 LBS @ BEARING USING #2. DOUG FIR CALES FROM WESTERN WOODS USE WE NEED 4 1/2 TO CARRY LOAD. RAFTERS AT HOUSE SIDE HAVE 5 SQ IN SO APPROVED. |
| 07/09/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1.) PLAN CALLS FOR 4 X 6 BEAM NOT 2 X 6. 2.) RAFTERS NOTCHED AT EXISTING WALL SO THAT ONLY 3" OF RAFTER DEPTH LEFT. 3" NOTCH EXTENDS UP TO 3" INTO PATIO AREA. PLEASE PROVIDE LOAD CALCULATIONS FOR THIS SIDE OF PATIO COVER AND INFORMATION INDICATING THAT SELECT #2 DOUG. WILL CARRY IMPOSED LOAD YOU MAY CALL DAVE WITT @ 791-5550 FOR THIS INFORMATION HE CAN CONTACT ME ON MY CELL PHONE. |
| 07/08/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1.) NO PLANS OR PERMITS @SITE. NO ONE ANSWERED KNOCK @ DOOR. |