Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/13/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/23/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0935*/ 1) STAIRS DO NOT COMPLY WITH IRC SECTION 314.2, EXCEED SHORTEST RISER 7 1/8" BY MORE THAN 3/8" - 7 3/4 + 2) YOU MUST PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION |
| 10/22/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0935*/ 1) STAIR RISERS EXCEED 3/8 GREATER THAN SMALLEST RISER BY 1", 6 7/8 TO 7 7/8 PER IRC 314.2 2) DEFUSER BOOT NOT BLOCKED 3 SIDES 3) BEARING STUDS DAMAGED AT RANGE HOOD NOTCHED GREATER THAN 1/4 DEPTH |
| 10/21/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) ITEMS 3,5, AND 7 FROM 10/18/02 INSPECTION NOT FIXED 2) SMOKE DETECTOR WITHIN 36" OF AIR REGISTER 3) BLOCK DEFUSER 3 SIDES 4) BEARING STUD DAMAGED AT RANGE HOOD |
| 10/18/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) KITCHEN SHEARWALL NOT NAILED ONE STUD 2) KITCHEN HORIZONTAL VENT NOT ALLOWED BELOW 42" 3) TRUSS HANGERS MISSING NAILS 4) ANCHOR BOLTS LOOSE MISSING THROUGHOUT 5) STAIR RISE EXCEEDS 3/8" BETWEEN STEPS 6) 2ND FLOOR GLUE LAM NOT BEARING ON TRIMMERS 7) BLOCK DEFUSER BOOTS 3 SIDES 8) JOIST HANGER MISSING 9) WALLS NOT ANCHORED 10) HEADERS MUST BEAR ON TRIMMERS 11) STOPPED INSPECTIONS |