Permit: T02CM03025


Addresses:

2944 N CARDELL CI

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
10/14/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
10/10/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) ITEM 5 FROM 10/08/02 NOT COMPLIED WITH 2) INSTALL 2ND FLOOR CS STRAPS PER SIMPSON 15" EACH SIDE OF SPLICES
10/08/2002 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) ADD BLOCKS AT 2 X RAFTERS AT GARAGE FRONT PERMETER NEXT TO GLU LAM, ALSO ADD BLOCKS SAME SHED ROOF WHERE OSB IS TURNED THE WRONG WAY 2) ADD WIND BRACING REAR WALL 1ST AND 2ND FLOOR 3) LARGE POP OUTS TO BE CONNECTED TO MAIN FRAME 16" ON CENTER VERTICALLY 4) REAR PORCH POST TO BEAM CONNECTION LAG BOLT LENGTH TO BE VERIFIED 5) TIE 45 DEGREE ANGLE (WALLS SHEAR) TOGETHER AT FRONT