Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) ALL FIXTURES TO BE CAULKED 408.2 94 UPC. 2.) ALL HOSE BIBBS TO HAVE ATMOSPHERIC VACCUM BREAKERS 602 94UPC 3.) N/H BAND NOT APPROVED LISTED CONNECTOR AT TRAP ARM 301.1.3 94 UPC 4.) TRAPS SHALL BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED. 1003.3 94 UPC THE TRAP ARM SHALL NOT CHANGE SIZE 5.) ALL SINKS REQUIRE CLEAN OUTS 707.4 UPC 6.) APPLIANCE CONNECTOR AT WATER HEATER EXCEEDS ALLOWABLE LENGTH 1212.0 94UPC 7.) VENT TERMINATION WITHIN 10' OF AIR INTAKE 906.2 94UPC 8.) WATER HEATER VENT TERMINATION 517 94 UPC. 9.) THIS INSPECTION COVERS ONLY VISIBLE WORK, AND DOES NOT INCLUDE ANY WORK PERFORMED WITHOUT PERMITS THAT HAS BEEN COVERED OR CONCEALED. 10.) ONLY ONE SLIP NUT ALLOWED ON OUTLET SIDE OF P-TRAP. |
|
| 01/06/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 07/01/2002 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |