Permit: T02CM03023

Parcel: 115081020

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/06/2003 ELECTRIC - FINAL Denied ELECT SERVICE UPGRADED WITHOUT PERMIT OR INSPECTION VERIFY 2ND GROUND ROD, GAS BOND IMPROPERLY CONNECTED, NO WATER BOND
2.) THE LIGHT ON THE GFI IN BATHROOM SHOULD NOT BE ON SAME CIR
3.) WE NEED TO REVIEW IN APPROVED SET OF PLANS.
4.) NEW WIRING BRANCH CIRCUITS HAVE BEEN PULLED INTO 200AMP PANEL. THE WIRING HAS NEVER BEEN INSPECTED.
DUE TO COMPLETE REWIRING AND NEW SERVICE AND ALL ITEMS FINISHED ELECTRICAL WORK NOT HAVING BEEN INSPECTED INSPECTOR WILL NOT ISSUE ANY TYPE OF CLEARANCE OR FINAL. IF NOT INSPECTED BEHIND WALLS AND CEILING I CANNOT GIVE ANY TYPE OF BOX.
07/01/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PLEASE PROVIDE PAPER WORK FOR SERVICE UPGRADE INSPECTION. 2.) WE ARE MISSING FACE PLATES. 3.) PLEASE VERIFY NEW WIREING WHEN WORK WAS DONE AND INSPECTIONS FOR THAT WORK. 4.) SMOKE DETECTORS ARE NEEDED. 5.) JUNCTION BOXES ARE NEEDED AT LIGHT FIXTURES 6.) WE HAVE GROUNDED RECEPTACLES ON AN ON GROUNDED SYSTEM. 7.) INSTALL AND SUPPORT LIGHT FIXTURES.