Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Not ready for Inspection
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 07/10/2002 |
REINFORCED MASONRY PRE-GROUT |
|
Not ready for Inspection |
IVRS - Inspection 0000*OK PRE-SLAB NO REBAR. |