Permit: T02CM03008

Parcel: 11720016G

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM03008

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/05/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
06/28/2002 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*1.) PROVIDE MIN 1 1/2" WIDE HANGER STRAP ON FLEX DUCT EVERY 5' PANDUIT STRAPS WILL NOT BE ACCEPTED AS HANGER STRAP. 3. PVC PIPE NOT ALLOWED IN PLENUM CEILING RECALL FOR INSPECTION.