Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM02987
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
11/15/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* OK FOR C OF O. |
|
11/13/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*60,000 BTUH PKG. HT. PUMP, FUSED AT 60 AMP. ELECT DATA PLATE INDICATES MARKED AT 5KW AUX. HEAT STRIP. 60 AMP FUSERS, FOR A HEAT PUMP 1ST STAGE HEAD AND A 5KW AUX HT STRIP ARE TO SMALL. CIRCUIT IS NOT LARGE ENOUGH FOR 2 APPLIANCES. 2.) CANNOT DUMP CONDENSATE DRAIN OUT A CONALIE WITHOUT A DOWN SPOUT. NEED TO CONTINUE CONDENSATE TO GROUND. 1.) REAR UNIT SOME AUX HT. STRIP PROBLEM. 2.) CANNOT TERMINATE CONDENSATE INTO WET VENT ON ROOF. CORRECT RECALL. |