Permit: T02CM02946

Parcel: 133243720

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/01/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) WASTE & VENT SYSTEM IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) OK FOR DRYWALL.
06/28/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) CAN NOT HAVE A HORIZONTAL VENT BELOW THE FLOOD RIM LEVEL OF FIXTURE FOR SHAMPOO SINKS. ALL HORIZONTAL VENTS MUST BE 6" ABOVE FLOOD RIM LEVEL.
06/26/2002 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*