Permit: T02CM02929

Parcel: 10510088Q

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM02929

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/04/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
10/30/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) SUPPORT WIRES NEEDED FOR EXIT LIGHTS AND 2 X 4 FIXTURES 110-16. 2.) SUPPORT M/C CABLE TO BE SUPPORTED AS PER CODE 334-18. 3.) CHECK CONDUCTOR FILL AND BOX FILL 370. 4.) SUPPORT ELECTRIC INDEPENDANLY AS PER CODE 300-11. 5.) PLEASE ATTACH FIXTURES TO GRID.
10/17/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PLEASE CALL FOR FINALS TO OCCUPY 1ST FLOOR. OK WALLS EAST HALF 2ND FLOOR. PLEASE RE OPEN FOR 2ND FLOOR INSPECTIONS.
09/18/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) STAIR WELL SOFFITT PIPING & BOXES. 2.) CONFERENCE ROOM WALLS 3.) MAIL ROOM WALLS. 4.) KITCHEN 5.) OFFICE PARTITIONS.