Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 08/02/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO WATER TEST ON SEWER AND VENT LINES 2) GAS PIPING LOOSE THROUGH TRUSSES. STRAP IT TO TRUSSES 3) PEX WATER LINES IN KITCHEN MUST BE A MINIMUM OF 12" FROM RECESSED LIGHT FIXTURE 4) NO WATER IN SUPPLY LINES 5) INSTALL FHA STRAP ACROSS MAIN GAS LINE ACROSS BROKEN BLOCK 6) SECURE PIPE CLAMP FOR MAIN LINE JUST BELOW ITEMS |