Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 10/28/2003 |
PLUMBING - YARD WTR LINE/TEST |
|
Approved |
IVRS - Inspection 0000*/ 1) BACKFLOW PREVENTOR HAS BEEN INSTALLED AND CONNECTED TO METER AND MANAFOLD. 2) OK TO BACKFILL TRENCH. |
| 09/22/2003 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection 0000*/1) HYDROSTATIC TEST 125 PSI IS OK. 2) YARD WATER LINE FROM RM #127 MECH ROOM TO METER LOCATION IS OK. 3) OK TO BACKFILL TRENCH. 4) MUST SEE FINAL CONNECTION TO METER AND BACKFLOW PREVENTOR. |