Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/06/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE P-TRAPS 2. PROPERLY TERMINATE CONDENSATE PIPING 6" ABOVE GRADE 3. PROVIDE OUTSIDE AIR INLET AND BALANCE PER PLANS 4. IDENTIFY UNIT DATA PLATE 5. PVC SUPPORTS NOT TO EXCEED 4' 6. NO WASTE VENTS WITHIN 10' OF OUTSIDE AIR INLET D&H HEAT & COOLING |
|
| 04/14/2008 | MECHANICAL - FINAL | Denied | ||
| 03/16/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |