Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2009 | ELECTRIC - ABOVE CEILING | Approved | ||
| 07/03/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* 1) SUPPORT MC CABLE PER NOC. WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS ( 334-10) 2) PROVIDE LETER OF APPROVAL FOR USE OF MC CABLE, FROM ARCH. | |
| 06/02/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* | |
| 04/30/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*THE MC CABLE IS NOT PROPERLY SUPPORTED. 2.) DO NOT USE PLASTIC TY RAPS TO SUPPORT MC OR ANY OTHER ELECTRICAL CABLE. |