Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*TEST OK ON COMPLETE SYSTEM. LAST INSP ON JOB PLEASE PROVIDE GAS CARD THANKS. |
|
| 01/03/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) PLEASE PROVIDE PLUMBING LICENSE NUMBER FOR GAS WORK PERFORMED ON THIS JOB. 2.) PLANS AND PERMIT TO BE ON JOB SITE AT ALL TIMES. 3.) MEDIUM PRESSURE GAS PIPING TO BE TESTED TO 60# MINIMUM FOR 30 MINTUES PER 1204,3.2 94UPC. 4.) GUAGE USED SHALL BE IN ONE POUND INCREMENTATION OR LESS PER 712.4 94 UPC. 5.) NO ACCESS TO ROOF TOP UNITS. |
|
| 12/24/2002 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection 0000*GAS PRESS TEST ON NEW LINE 20 PSI. |